GE GFK-1541B Network Card User Manual


 
GFK-1541B Chapter 3 Programming Channel Commands 3-39
3
Minor Error Codes for Major Error Codes 5H and 85H (Continued)
Error Status Service Request Error Description
(Hexadecimal)
F705H/F785H Required to log in to a task for service.
F805H/F885H Invalid task name referenced.
F905H/F985H Task address out of range.
FC05H/FC85H I/O configuration is invalid.
FE05H/FE85H No privilege for attempted operation.
FF05H/FF85H Service request has been aborted.
Minor Error Codes for Major Error Code 11H (at Remote Server PLC)
Error Status
(Hexadecimal)
SRTP Error Description
Error codes common to all GE Fanuc PLCs
0111H Generic SRTP error.
0211H The PLC is inaccessible.
0311H Reserved.
0411H Unexpected SRTP version encountered in received message.
0511H Unrecognized SRTP message received.
0611H Data present in SRTP message which should not contain data.
0711H Generic resource problem detected.
0811H SRTP message encountered in inappropriate connection state.
0911H Generic refusal by backplane driver to handle request.
0A11H Recognized but unsupported SRTP message received.
0B11H Lost transaction in server.
0C11H Error sending SRTP PDU to the client PLC.
Can someone explain the disclaimer below? This manual describe those four
products.
Error codes specific to IC697CMM742, IC693CMM321, IC693CPU364, and
IC693CPU374
1411H Unable to allocate a text buffer from dual port memory.
1711H Invalid text length detected in a mailbox message.
1811H Invalid number of destinations detected in a mailbox message.
1911H Invalid source detected in a mailbox message.
1A11H Invalid slot number detected in a mailbox message.
1B11H Invalid rack number detected in a mailbox message.
1D11H Bad text buffer address in dual port memory.
2111H Unable to find control data required to send a mailbox message to the PLC.
2211H Timed out waiting for availability of mail communications with the PLC.
2311H Invalid task ID detected while attempting to send a mailbox message to the PLC.
2411H Unable to send mailbox message to PLC because the mail queue is full.
2611H Unable to communicate with PLC.
2711H Backplane driver not initialized or unable to acquire a dual port memory
semaphore.
2A11H The backplane driver could not access the PLC.
2B11H Invalid binding on the message sent to the backplane driver.
2C11H The message could not be sent to its destination because the mailbox was not open.
2D11H The maximum number of transfers to the destination is already taking place.