2-10 TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual
May 2002 GFK-1541B
2
10.0.0.1 First PLC
10.0.0.2 Second PLC
10.0.0.3 Third PLC
..
..
10.0.0.255 PLC Programmer TCP or host
Also, in this case, set the subnet mask, gateway IP address, and name server IP address to 0.0.0.0.
Note
If the isolated network is ever connected to another network, the IP addresses
10.0.0.1 through 10.0.0.255 must not be used and the subnet mask, gateway IP
address, and name server IP address must be assigned by the network
administrator. The IP addresses must be assigned so that they are compatible
with the connected network. Refer to Chapter 6, “Network Administration
Support”, for more information on addressing.
See also “Determining If an IP Address Has Already Been Used”.
Converter:
Allows you to account for the power consumption added by a serial port converter
(measured in Watts). Choices are 0, 0.50, and 0.60.
AAUI Transceiver (Watts):
If you use an AAUI transceiver, allows you to account for the power
that the transceiver draws from the port (measured in Watts). The valid range is 0.25 to 2.00.
The default value is 0.50.
Station Manager PortParameters
Data Rate (bps):
Data rate (bits per second) for the port. Choices are 300, 600, 1200, 2400,
4800, 9600‡, or 19200*.
Parity:
Type of parity to be used for the port. Choices are None‡, Even, or Odd*.
Stop Bits:
Enter the number of stop bits. Choices are 1*‡ or 2.
Flow Control:
This parameter is currently not used by the Ethernet Interface. Changing this
parameter has no effect.
Turnaround Delay:
Turnaround delay time (in milliseconds) to be used for the port. Choices
are None*‡, 10 ms, 100 ms, or 500 ms.
Timeout:
This parameter is currently not used by the Ethernet Interface. Changing this
parameter has no effect.
* Default selection for the Software Loader Port.
‡ Default selection for the Station Manager Port.