IBM 9306 Personal Computer User Manual


 
Power cables
Power cables that you use to connect a system, storage expansion unit, and other
devices to the Rack PDU usually come with those devices. The following table
contains a list of power cables that you can use with the Rack PDU:
Length Cable rating Plug type Cable part #
2.8 m (9.2 ft) 250 V, 10 A IEC 320-C13 to IEC 320-C14 36L8886
4.3 m (14 ft) 250 V, 10 A IEC 320-C13 to IEC 320-C14 94G7448
Power cables that you use to connect your Rack PDU to a UPS or Front-end PDU
come with those devices as indicated in the following table:
Length
Cable
rating Plug type
Cable
part # Comes with:
2 m (6.6 ft) 250 V, 16 A IEC 320-C19 to IEC
320-C20
00N7700 APC SU-5000 RMB
UPS
(2 cables)
1 m (3.3 ft) 250 V, 16 A IEC 320-C19 to IEC
320-C20
00N7698 Front-end PDU (3
cables)
144 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308