5. Install the 1U blank filler panel 1 on the front of the rack cabinet at the same
U level as the Rack PDU. Use two M6 screws that come with this option.
Installing two devices horizontally
Use the following procedure to mount two Rack PDUs horizontally in your rack
cabinet:
1. Refer to the documentation that comes with your rack cabinet for additional
information.
Notes:
a. Removing the rack doors and side panels might make your Rack PDU
installation easier.
b. Use clip nuts for rack cabinets with round holes; use cage nuts for rack
cabinets with square holes.
Cage
nuts
Cage
nuts
Clip
nuts
2. Attach a dual-device attachment bracket 6 to the right side of one of the Rack
PDUs with two M3x5 screws; then, attach another dual-device attachment
bracket 5 to the left side of the other Rack PDU with two M3x5 screws.
Notes:
a. When you install two Rack PDUs next to each other, you will need some
parts from both options.
b. Turn the second dual-device attachment bracket 5 so that the threaded
holes are on the opposite side of the device as the holes on the other
attachment bracket 6.
160 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308