IBM 9306 Personal Computer User Manual


 
Rack PDU specifications
When connected to a dedicated power source, the Rack PDU conforms to UL950,
CSA 22.0-950, EN-60950, and IEC-950 standards. The following table contains the
product specifications for the Rack PDU:
Height 43 mm (1.7 in.)
Width 192 mm (7.5 in.)
Depth 221 mm (8.7 in.)
Weight 2.4 kg (5.4 lbs)
Operating temperatures 10°C–35°C (50°F–95°F) at 0–914 m (0–3000 ft)
10°C–32 °C (50°F–90°F°) at 914–2133 m (3000–7000 ft)
Operating humidity 8–80% (non-condensing)
Rated voltage 100–127 V ac, 15 A, single-phase
200-240 V ac, 10 A, single-phase
Rated frequency 50–60 Hz
Maximum power rating 2400 VA
Power inlet Two IEC 320-C20 inlets rated at 16 A (VDE) / 20 A
(UL/CSA)
Transfer time <35 ms from main to backup power
Power outlets Four IEC 320-C13 outlets rated at 10 A (VDE) / 15 A
(UL/CSA)
168 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308