Schneider Electric vw3-a58101 Electronic Accessory User Manual


 
78
ENGLISH
Adjust Menu
The following parameters can be accessed once the I/O have been reassigned on the basic product.
(1) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for "high torque" applications.
Code Description Adjustment range Factory setting
AA
AA
CC
CC
22
22
Accel. 2 - s
0.05 to 999.9 5 s
2nd acceleration ramp
dd
dd
EE
EE
22
22
Decel. 2 - s
0.05 to 999.9 5 s
2nd deceleration ramp
These parameters can be accessed if the ramp switching time (parameter Frt) is other than 0 Hz or
if a logic input is assigned to ramp switching.
II
II
dd
dd
CC
CC
DC Inj.curr - A
0.10 to 1.36 In (1) Acc. to controller rating
DC injection braking current
This parameter can be accessed if a logic input is assigned to DC injection stopping.
After 30 seconds the injection current is peak limited to 0.5 Ith if it is set at a higher value
SS
SS
PP
PP
22
22
Preset Sp.2 - Hz
LSP to HSP 10 Hz
2nd preset speed
SS
SS
PP
PP
33
33
Preset Sp.3 - Hz
LSP to HSP 15 Hz
3rd preset speed
SS
SS
PP
PP
44
44
Preset Sp.4 - Hz
LSP to HSP 20 Hz
4th preset speed
SS
SS
PP
PP
55
55
Preset Sp.5 - Hz
LSP to HSP 25 Hz
5th preset speed
SS
SS
PP
PP
66
66
Preset Sp.6 - Hz
LSP to HSP 30 Hz
6th preset speed
SS
SS
PP
PP
77
77
Preset Sp.7 - Hz
LSP to HSP 35 Hz
7th preset speed
JJ
JJ
OO
OO
GG
GG
Jog Freq. - Hz
0 to 10 Hz 10 Hz
Jog frequency
JJ
JJ
GG
GG
tt
tt
JOG Delay - s
0 to 2 s 0.5 s
Anti-BrkLgSeqFlwd delay between two consecutive jog operations
bb
bb
rr
rr
LL
LL
BrReleaseLev- Hz
0 to 10 Hz 0 Hz
Brake release frequency
II
II
bb
bb
rr
rr
BrRelease I - A
0 to 1.36In(1) 0 A
Brake release current
bb
bb
rr
rr
tt
tt
BrReleasTime- s
0 to 5 s 0 s
Brake release time
bb
bb
EE
EE
nn
nn
BrEngage Lev- Hz
0 to LSP 0 Hz
Brake engage frequency
bb
bb
EE
EE
tt
tt
BrEngageTime- Hz
0 to 5 s 0 s
Brake engage time
GP_ATV58_EN.fm Page 78 Mardi, 2. avril 2002 6:09 18