Schneider Electric vw3-a58101 Electronic Accessory User Manual


 
81
ENGLISH
Drive Menu
This menu can be accessed when the switch is in position .
The parameters can only be modified in stop mode with the speed controller locked.
Drive performance can be optimized by :
- entering the values given on the rating plate in the drive menu
- performing an auto-tune operation (on a standard asynchronous motor)
When using special motors (motors connected in parallel, tapered rotor brake motors, synchronous or
synchronized asynchronous motors, rheostatic rotor asynchronous motors) :
- Select the “Hdg : Handling” or the “GEn : General Use” macro-configuration.
- Set the “SPC” Special motor parameter to “Yes” in the drive menu.
- Adjust the “UFr” IR compensation parameter in the adjust menu to obtain satisfactory operation.
(1) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for "high torque" applications.
(2) according to position of 50/60Hz switch.
Code Description Adjustment range Factory setting
UU
UU
nn
nn
SS
SS
Nom.Mot.Volt - V
200 to 240V
200 to 500 V
230 V (2)
400/460V (2)
Nominal motor voltage given on the rating plate
The adjustment range depends on the speed controller model :
ATV58••••M2
ATV58••••N4
FF
FF
rr
rr
SS
SS
Nom.Mot.Freq- Hz
10 to 500 Hz 50/60Hz (2)
Nominal motor frequency given on the rating plate
nn
nn
CC
CC
rr
rr
Nom.Mot.Curr - A
0.25 to 1.36 In (1) acc. to controller rating
Nominal motor current given on the rating plate
nn
nn
SS
SS
PP
PP
Nom.MotSpeed-rpm
0 to 9999 rpm acc. to controller rating
Nominal motor speed given on the rating plate
CC
CC
OO
OO
SS
SS
Mot. Cos Phi
0.5 to 1 acc. to controller rating
Motor Cos Phi given on the rating plate
tt
tt
UU
UU
nn
nn
Auto Tuning
No - Yes No
Used to auto-tune motor control once this parameter has been set to “Yes”.
Once auto-tuning is complete, the parameter automatically returns to “Done”, or to “No” in the event
of a fault.
Caution : auto-tuning is only performed if no command has been activated. If a "freewheel stop" or
"fast stop" function is assigned to a logic input, this input must be set to 1 (active at 0).
tt
tt
FF
FF
rr
rr
Max. Freq. - Hz
10 to 500 Hz 60/72Hz (2)
Maximum output frequency.
The maximum value is a function of the switching frequency. See SFR parameter (drive menu).
nn
nn
LL
LL
dd
dd
Energy Eco
No-Yes Yes
Optimizes motor efficiency.
Can only be accessed in the variable torque macro-configuration.
GP_ATV58_EN.fm Page 81 Mardi, 2. avril 2002 6:09 18