Schneider Electric vw3-a58101 Electronic Accessory User Manual


 
108
ENGLISH
Maintenance
Fault displayed Probable cause Procedure, remedy
PP
PP
HH
HH
FF
FF
Mains Phase Loss
speed controller incorrectly supplied or
fuses blown
transient fault on one phase
use on a single phase supply of an
ATV58•U72M2, U90M2 or a D12M2
(3-phase)
check the power connection and the fuses
•reset
configure the "In Phase Loss" (code
IPL) fault to "No", in the FAULT menu
UU
UU
SS
SS
FF
FF
Undervoltage
line supply too low
transient voltage dip
damaged load resistor
check the line voltage
change the load resistor
OO
OO
SS
SS
FF
FF
Overvoltage
line supply too high check the line voltage
OO
OO
HH
HH
FF
FF
Drive Overheat
heatsink temperature too high
(
tt
tt
HH
HH
dd
dd
>118 %)
monitor the motor load, the speed
controller ventilation and wait for it to
cool down before resetting
OO
OO
LL
LL
FF
FF
Mot Overload
•thermal trip due to prolonged overload
(
tt
tt
HH
HH
rr
rr
>118 %)
check the thermal protection setting,
monitor the motor load
•a reset will be possible after approximately
7 minutes
OO
OO
bb
bb
FF
FF
Overbraking
•braking too sudden or driving load
supply overvoltage during operation
•increase the deceleration time, add a
braking resistor if necessary
check the possible supply overvoltage
OO
OO
PP
PP
FF
FF
Motor Phase Loss
one phase cut at the speed controller
output
Check the motor connections and the
operation of the output contactor (if fitted)
If a motor starter is used in macro
configuration, check the configuration of
the relay R2 and the output contactor
LL
LL
FF
FF
FF
FF
Loss Follower
•loss of the 4-20mA setpoint on input AI2 check the connection of the setpoint
circuits
OO
OO
CC
CC
FF
FF
Overcurrent
•ramp too short
•inertia or load too high
mechanical locking
check the settings
check the size of the motor/speed
controller/load
check the state of the mechanism
SS
SS
CC
CC
FF
FF
Short Circuit
short-circuit or grounding at the speed
controller output
check the connection cables with the
speed controller disconnected, and the
motor insulation. Check the speed
controller transistor bridge
CC
CC
rr
rr
FF
FF
Precharge Fault
•load relay control fault
damaged load resistor
check the connectors in the speed
controller and the load resistor
SS
SS
LL
LL
FF
FF
Serial Link Flt
•incorrect connection on the speed
controller terminal port
check the connection on the speed
controller terminal port
OO
OO
tt
tt
FF
FF
Motor Overheat
motor temperature too high (PTC
probes)
check the motor ventilation and the ambi-
ent temperature, monitor the motor load
check the type of probes used
tt
tt
SS
SS
FF
FF
PTC Therm Sensor
•incorrect connection of probes to the
speed controller
check the connection of the probes to
the speed controller
check the probes
GP_ATV58_EN.fm Page 108 Mardi, 2. avril 2002 6:09 18