AMX NI-3101-SIG Switch User Manual


 
Connections and Wiring
10
NI-3101-SIG Signature Series NetLinx Integrated Controller
Using the 4-pin mini-Phoenix connector for data and power
Connect the 4-pin 3.5 mm mini-Phoenix (female) captive-wire connector to an external NetLinx device as
shown in FIG. 5.
Using the 4-pin mini-Phoenix connector for data with external power
To use the 4-pin 3.5 mm mini-Phoenix (female) captive-wire connector for data communication and power
transfer, the incoming PWR and GND cable from the 12 VDC-compliant power supply must be connected to
the AXlink cable connector going to the device (FIG. 6). Always use a local power supply to power the device.
Make sure to connect only the GND wire on the AXlink/PWR connector when using a separate
12 VDC power supply. Do not connect the PWR wire to the AXlink connector’s PWR (+) opening.
FIG. 4 2-pin mini-Phoenix connector wiring diagram (direct power)
FIG. 5 Mini-Phoenix connector wiring diagram (direct data and power)
FIG. 6 4-pin mini-Phoenix connector wiring diagram (using external power source)
PWR +
GND -
Integrated Controller
Power Supply
To the Integrated Controller’s
To the external AXlink device
AXlink/PWR connector
PWR +
AXP/TX
AXM/RX
GND -
Top view
Top view
PWR +
AXP/TX
AXM/RX
GND -
PWR (+)
GND (-)
Local +12 VDC
(coming from
To the Integrated Controller’s
To the external AXlink device
AXlink/PWR connector
power supply
an external
power supply)
Top view
Top view
AXP/TX
AXM/RX
GND -
AXP/TX
AXM/RX
GND -
When you connect an external power supply, do not connect the wire from the PWR
terminal (coming from the external device) to the PWR terminal on the Phoenix
connector attached to the Controller unit. Make sure to connect only the AXM, AXP,
and GND wires to the Controller’s Phoenix connector when using an external power
supply.