6-4 XEROX DOCUPRINT 96/4635/180 IPS INSTALLATION PLANNING GUIDE
Printer outlet voltages50 Hz
All power outlets must have a dedicated circuit for each system
equipment piece. Make sure each power cord has a separate circuit.
Note: Consult with your service representative to determine the
type of plug and receptacle to be used for your 50 Hz system.
DELTA configurations50 Hz For 50 Hz DELTA configurations, measure the DELTA connection
voltages at the power source.
WYE (or Star) configurations50 Hz For the 50 Hz WYE configuration, measure the WYE or Star
connection voltages at the power source.
Table 6-3.Printer (50 Hz) DELTA voltage
Service outlet
configuration Measurement Nominal Range
4 Wire 220 V Line 1 to line 2 220 V RMS 198-242 V RMS
4 Wire 220 V Line 2 to line 3 220 V RMS 198-242 V RMS
4 Wire 220 V Line 1 to line 3 220 V RMS 198-242 V RMS
4 Wire 230 V Line 1 to line 2 230 V RMS 207-253 V RMS
4 Wire 230 V Line 2 to line 3 230 V RMS 207-253 V RMS
4 Wire 230 V Line 1 to line 3 230 V RMS 207-253 V RMS
5 Wire 240 V Line 1 to line 2 240 V RMS 216-264 V RMS
5 Wire 240 V Line 2 to line 3 240 V RMS 216-264 V RMS
5 Wire 240 V Line 1 to line 3 240 V RMS 216-264 V RMS
Table 6-4.Printer (50 Hz) WYE (Star) 415 voltage
Service outlet
configuration Measurement Nominal Range
5 Wire 415 V Line 1 to line 2 415 V RMS 374-457 V RMS
5 Wire 415 V Line 2 to line 3 415 V RMS 374-457 V RMS
5 Wire 415 V Line 1 to line 3 415 V RMS 374-457 V RMS
5 Wire 415 V Line 1 to neutral 240 V RMS 216-264 V RMS
5 Wire 415 V Line 2 to neutral 240 V RMS 216-264 V RMS
5 Wire 415 V Line 3 to neutral 240 V RMS 216-264 V RMS