Xerox 4635 Printer User Manual


 
PREINSTALLATION
Table 3-8. System controller and peripheral cabinet
power receptacle requirements
Electrical environment Voltage Current Receptacle
U.S. and Canada 60 Hz 208/240, 1 Phase or
220/230 (L1-L2)
15A NEMA 6-15R
or ANSI C73,
20R
International 50 Hz 220/2301 Phase 15A Per local code
50 Hz WYE printer outlet voltages
Note: All power outlets must be dedicated only to this
equipment. Ensure that each power cord has a separate circuit.
50 Hz WYE configurations only: Measure the WYE connection
voltages at the power source. Table 3-9 shows 415 voltages.
Table 3-10 shows 380 and 400 voltages.
Table 3-9. Printer (50 Hz only) WYE connection for 415 V
Service outlet
Service outlet
configuration Measurement Nominal Range
5 Wire 415 V Line 1 to Line 2 415 V RMS 374-457 V RMS
5 Wire 415 V Line 2 to Line 3 415 V RMS 374-457 V RMS
5 Wire 415 V Line 1 to Line 3 415 V RMS 374-457 V RMS
5 Wire 415 V Line 1 to Neutral 240 V RMS 216-264 V RMS
5 Wire 415 V Line 2 to Neutral 240 V RMS 216-264 V RMS
5 Wire 415 V Line 3 to Neutral 240 V RMS 216-264 V RMS
XEROX 4635 LASER PRINTING SYSTEM INSTALLATION PLANNING GUIDE 3-17