7 Dip switch positions (if applica-
ble)
See below
8 Register #3 See below
9 Line quality “FF” acceptable, “00” unaccept-
able
> Number of external battery packs
attached
SmartCell models: “nnn” where
nnn is how many external packs
are connected Non-SmartCell
units: whatever has been set with
>+ and >- by the user
Matrix
UPS
(and
pos-
sibly
Sym-
metra)
specific
com-
mands
ˆ Run in bypass mode If online, “BYP” is received as by-
pass mode starts If already in by-
pass, “INV” is received and UPS
goes online “ERR” received if UPS
is unable to transfer
< Number of bad battery packs “nnn” - count of bad packs con-
nected to the UPS
/ Load current “nn.nn” - true RMS load current
drawn by UPS
\ Apparent load power “nnn.nn” - output load as percent-
age of full rated load in VA.
ˆV Output voltage selection (ed-
itable)
“A” - automatic according to in-
put tap, “M” - 208 VAC, “I” - 240
VAC
ˆL Front panel language “E” - English, “F” - French, “G”
- German, “S” - Spanish, “1” “2”
“3” “4” - ?
w Run time conservation “NO” (disabled) or “02” “05”
“08” - minutes of runtime to
leave in battery (UPS shuts down
“early”)