APC UPS control system Power Supply User Manual


 
DFO == (4)-all-countries (D)omestic (I)nternational (A)sia (J)apan
(M) North America - servers.
RSP == Total number possible answers returned by a given CMD.
FSZ == Max. number of field positions to be filled.
FVL == Values that are returned and legal.
Programming the UPS EEPROM
There are at this time a maximum of 12 different values that can be pro-
grammed into the UPS EEPROM. They are:
Item Command Meaning
1. c The UPS Id or name
2. x The last date the batteries were replaced
3. u The Upper Transfer Voltage
4. l The Lower Transfer Voltage
5. e The Return Battery Charge Percentage
6. o The Output Voltage when on Batteries
7. s The Sensitivity to Line Quality
8. p The Shutdown Grace Delay
9. q The Low Battery Warning Delay
10. k The Alarm Delay
11. r The Wakeup Delay
12. E The Automatic Self Test Interval
The first two cases (Ident and Batt date) are somewhat special in that you
tell the UPS you want to change the value, then you supply 8 characters that
are saved in the EEPROM. The last ten item are programmed by telling
the UPS that you want it to cycle to the next permitted value.
In each case, you indicate to the UPS that you want to change the EEPROM
by first sending the appropriate query command (e.g. “c” for the UPS ID
or “u” for the Upper Transfer voltage. This command is then immediately
followed by the cycle EEPROM command or “-”. In the case of the UPS Id
or the battery date, you follow the cycle command by the eight characters
that you want to put in the EEPROM. In the case of the other ten items,
there is nothing more to enter.
The UPS will respond by “OK” and approximately 5 seconds later by a
vertical bar (—) to indicate that the EEPROM was changed.
199