Black Box TS1002A Barcode Reader User Manual


 
84
OMNISCANNER
Press or to toggle between the Return Loss results for
OMNIScanner and OMNIRemote.
Press (Graph) to display the Return Loss graph for the highlighted pair.
The Return Loss is displayed for the frequency indicated by the cursor position.
Press (Pairs) to view Return Loss graphs for other pairs.
Press (Diagnostics) to display the TDRL screen, where cabling and/or
connection faults can be identified. (See Chapter 6, Diagnostics, for further
information.)
Press ESC to exit the RETURN LOSS screen.
5.3.6 ELFEXT
ELFEXT (Equal Level Far End Cross Talk) measures the electromagnetic coupling
at the far end and normalizes the result to account for the cable’s attenuation.
ELFEXT is reported in dB and results are computed for twelve pair combinations
at the OMNIScanner and OMNIRemote end of the cabling.
In the ELFEXT screen, the worst case margin for all near and far pair
combinations is shown at the top of the screen.
The pair combinations are displayed in the column on the left side, followed by
the ELFEXT value, the margin/limit, and the frequency. The result for each pair
combination is tagged with a PASS or FAIL indicator.