Delta Electronics DOP-A/AE/AS Network Card User Manual


 
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
Revision January, 2008, Doc. Name: 2007PDD23000007 1-103
CrossReference Table (Inter Memoryof Delta HMI and Modbus Reference Address)
Inter Memory
of Delta HMI
Modbus Reference
Address
Supporting Modbus
Function
Address of Function
$0 40001 03H, 06H, 10H 0000H
$1 40002 03H, 06H, 10H 0001H
.
.
.
$1023 41024 03H, 06H, 10H 03FFH
$M0 42001 03H, 06H, 10H 07D0H
$M1 42002 03H, 06H, 10H 07D1H
.
.
.
$M1023 43024 03H, 06H, 10H 0BCFH
RCPNO 44001 03H, 06H 0FA0H
RCP0 45001 03H, 06H, 10H 1388H
RCP1 45002 03H, 06H, 10H 1389H
.
.
.
$2000.0 00001 01H, 05H, 0FH 0000H
$2000.1 00002 01H, 05H, 0FH 0001H
.
.
.
$2000.15 00016 01H, 05H, 0FH 000FH
$2001.0 00017 01H, 05H, 0FH 0010H
.
.
.
$2063.0 01009 01H, 05H, 0FH 03F0H
.
.
.
$2063.15 01024 01H, 05H, 0FH 03FFH
$M200.0 01025 01H, 05H, 0FH 0400H