Delta Electronics DOP-A/AE/AS Network Card User Manual


 
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
1-114 Revision January, 2008, Doc. Name: 2007PDD23000007
Omron C Series PLC Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 2.
Controller station number: 0.
Control area/status area: DM0 / DM10.
¾ This driver can support OMRON C/CPM series PLC simultaneously.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Word No. Bit No.
Data length
IR area IRn n: 0 ~ 511 N/A Word
HR area HRn n: 0 ~ 99 N/A Word
AR area ARn n: 0 ~ 27 N/A Word
LR area LRn n: 0 ~ 63 N/A Word
TC area TCn n: 0 ~ 511 N/A Word
DM area DMn n: 0 ~ 6655 N/A Word
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
IR area IRnb n: 0 ~ 511 b: 00 ~ 15
HR area HRnb n: 0 ~ 99 b: 00 ~ 15
AR area ARnb n: 0 ~ 27 b: 00 ~ 15
LR area LRnb n: 0 ~ 63 b: 00 ~ 15
TC area TCn N/A n: 0 ~ 511
C. Connections (Connector Pinouts)
RS-232
1:1 Host Link via RS-232C converter
DOP Series
9 pin D-SUB male (RS-232)
Controller
9 pin D-SUB male (RS-232)
Controller
9 pin D-SUB male (RS-232)
RXD (2)
(2) TXD
TXD (3)
GND (5)
(3) RXD
(9) SG
(4) RS
(5) CS
Top View
Pin1