Delta Electronics DOP-A/AE/AS Network Card User Manual


 
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
1-34 Revision January, 2008, Doc. Name: 2007PDD23000007
GE Fanuc 90 Series SNP PLC Back to Table
A. HMI factory settings
Baud rate: 19200, 8, ODD, 1.
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: %R1 / %R10.
NOTE
1) Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication
is allowed.
2) If the PLC enabled “Check Password” function, the user needs to set the password by clicking Option >
Configuration > Communication. The user can find Controller Settings and set PLC password on
Communication Tab in the Configuration dialog box. Please enter a 4-digit password (If entering a
password that exceeds 4-digit number, only the first 4-digit number is valid).
B. Definition of controller Read/Write address
Registers
Read/Write range
Register Type Format
Word No. Bit No.
Data length
Discrete Inputs %In n: 1 ~ 12288 N/A Word (the multiple of 16 + 1)
Discrete Outputs %Qn n: 1 ~ 12288 N/A Word (the multiple of 16 + 1)
Discrete Temporaries %Tn n: 1 ~ 256 N/A Word (the multiple of 16 + 1)
Discrete Internals %Mn n: 1 ~ 12288 N/A Word (the multiple of 16 + 1)
%SA Discretes %SAn n: 1 ~ 128 N/A Word (the multiple of 16 + 1)
%SB Discretes %SBn n: 1 ~ 128 N/A Word (the multiple of 16 + 1)
%SC Discretes %SCn n: 1 ~ 128 N/A Word (the multiple of 16 + 1)
%S Discretes %S-n n: 1 ~ 128 N/A Word (the multiple of 16 + 1)
Genius Global Data %Gn n: 1 ~ 7680 N/A Word (the multiple of 16 + 1)
Registers %Rn n: 1 ~ 16384 N/A Word
Analog Inputs %AIn n: 1 ~ 8192 N/A Word
Analog Outputs %AQn n: 1 ~ 8192 N/A Word