Delta Electronics DOP-A/AE/AS Network Card User Manual


 
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
Revision January, 2008, Doc. Name: 2007PDD23000007 1-123
Read/Write Range
Register Type Format
Word No. Bit No.
Output Image QWn n: 0 ~ 65534 N/A
Output Image QDn n: 0 ~ 65532 N/A
Internal Bits MWn n: 0 ~ 65534 N/A
Internal Bits MDn n: 0 ~ 65532 N/A
Data Area DBm.DBWn n: 0 ~ 65534 m: 1 ~ 255
DBm.DBDn n: 0 ~ 65532 m: 1 ~ 255
Data Area (DB10) DBWn n: 0 ~ 65534 N/A
DBDn n: 0 ~ 65532 N/A
VWn n: 0 ~ 65534 N/A
VDn n: 0 ~ 65532 N/A
Timer
Tn n: 0-65535 N/A
Counter
Cn n: 0-65535 N/A
NOTE
1) The valid digit number of the value for the T(Timer) and C(Counter) is 3-digits only. Therefore, please
enter a 3-digit number. If entering a number that exceeds 3 digits, only the first 3 digits are valid (decimal
format). The other digits of the value for the T(Timer) will be replaced as 0 and the other digits of the
value for the C(Counter) will be abandoned. For example, assume that the users enter the value “12345”,
the actual write value for the T(Timer) will be “12300” and the actual write value for the C(Counter) will be
“123”.
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Input Image In.b n: 0 ~ 65535 b: 0 ~ 7
Output Image Qn.b n: 0 ~ 65535 b: 0 ~ 7
Internal Bit Mn.b n: 0 ~ 65535 b: 0 ~ 7
Data Area Bit DBm.DBXn.b n: 0 ~ 65535 b: 0 ~ 7
m = 1 ~ 255
Data Area Bit (10 DB) DBXn.b n: 0 ~ 65535 b: 0 ~ 7
Vn.b n: 0 ~ 65535 b: 0 ~ 7
NOTE
1) For all contacts when performing “Multiple Duplicate” function:
y If it exceeds 65535 when increasing, it will be regarded as 0.
y If it is less than 0, it will be regarded as 655XX.