Contacts
Read/Write range
Contact Type Format
Word No. Bit No.
Discrete Inputs %In N/A n: 1 ~ 12288
Discrete Outputs %Qn N/A n: 1 ~ 12288
Discrete Temporaries %Tn N/A n: 1 ~ 256
Discrete Internals %Mn N/A n: 1 ~ 12288
%SA Discretes %SAn N/A n: 1 ~ 128
%SB Discretes %SBn N/A n: 1 ~ 128
%SC Discretes %SCn N/A n: 1 ~ 128
%S Discretes %-Sn N/A n: 1 ~ 128
Genius Global Data %Gn N/A n: 1 ~ 7680
C. Connections (Connector Pinouts)
RS-232
DOP
9 pin D-SUB male
(RS-232)
Controller
RJ-45 cable connector
(RS-232)
Controller
RJ-45 cable connector
(RS-232)
RXD (2) (5) TXD
TXD (3)
GND (5)
(6) RXD
(4) GND
Top View
8
1
RS-422
DOP Series
9 pin D-SUB male (RS-232)
Controller
15 pin male (RS-232)
Controller
15 pin male (RS-232)
RXD+ (2)
(13) SD(B')
TXD+ (3)
TXD- (4)
(11) RD(B)
(10) RD(A)
(6) RTS(A)
(15) CTS(A')
RXD- (1
)
(12 ) SD (A')
(8) CTS(B)
(14) RTS(B')
(9) RD( *)
(NOTE 1)
Top View
NOTE
1) (9) RD(*) should be connected to 10(RD)(A) in serial. But if connecting PLC model is Series 90-70 PLC
IC697CPU731 and IC697CPU771, (9) RD(*) needs to be connected to 11(RD)(B).
Pin1