A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
Controller station number: 0.
Control area/status area: D0 / D10.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Word No. Bit No.
Data length
Auxiliary Relay Mn n: 0 ~ 3064 N/A Byte
Special Auxiliary Relay Mn n: 8000 ~ 8248 N/A Byte
Status Relay Sn n: 0 ~ 992 N/A Byte
Input Relay Xn n: 0 ~ 360(octal) N/A Byte
Output Relay Yn n: 0 ~ 360(octal) N/A Byte
Timer PV Tn n: 0 ~ 255 N/A Word
16-bit Counter PV Cn n: 0 ~ 199 N/A Word
32-bit Counter PV Cn n: 200 ~ 255 N/A Double Word
Data Register Dn n: 0 ~ 7999 N/A Word
Special Data Register Dn n: 8000 ~ 8255 N/A Word
Auxiliary Relay / Special Auxiliary Relay / Status Relay / Input Relay / Output Relay: Address must be the
multiple of 8.
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Auxiliary Relay Mn N/A n: 0 ~ 3071
Special Auxiliary Relay Mn N/A n: 8000 ~ 8255
Status Relay Sn N/A n: 0 ~ 999
Input Relay Xn N/A n: 0 ~ 377(octal)
Output Relay Yn N/A n: 0 ~ 377(octal)
Timer Flag Tn N/A n: 0 ~ 255
Counter Flag Cn N/A n: 0 ~ 255