Chapter 5 Operating SCU 35
ACTURA Flex 48330 Power System User Manual
5.2 Operation Procedures
After the system is powered on for the first time, you should set the system type
according to the actual configuration. The monitoring module will restart after the
system type is changed. In that case, you should re-configure those parameters
whose default values are inconsistent with the actual situation. Only after that can
the monitoring module operate normally.
After configuring the system parameters, you can carry out various operations
directly without resetting the parameter values. As for those important parameters
related to battery management, such as BLVD, you should be fully aware of their
influence upon the system before you change their values.
Note
For the exact meanings of the abbreviations used in LCD displayer, see Appendix E
Glossary.
1. The LCD will prompt you to select a language once the monitoring module is
powered on.
英文
English
You can use “
”, “”, “” or “” to select the language you want, and press
“ENT” to confirm.
2. The monitoring module will prompt you to wait, and start initialization.
Waiting……..
3. The first system information page appears
The system information is shown in many pages. You can repeatedly press “
” to
view other system information pages in a cycle.
2004-09-16
53.5V 125 A
System: No alarm
Auto /BC