Emerson 48330 Power Supply User Manual


 
Chapter 5 Operating SCU 57
ACTURA Flex 48330 Power System User Manual
LLVD Enable: Y
BLVD Enable: Y
LVD Mode:
Voltage
LVD Vlotage
LLVD: 44.0
BLVD: 43.2
LVD Time
LLVD: 300min
BLVD: 600min
Use “
” or “” to select one page or one of the parameters, and “” or “” to
select the parameter value. Press “ENT” to confirm and save.
Note
Generally you do not need to set the LVD parameters’ value. The defaults will do.
3. The value description of the LVD parameters is listed below.
Table 5-11 Value description of the LVD parameters
Parameter Range Default Value description
LLVD Enable Select “Y” to enable LLVD function
BLVD Enable
Y, N Y
Select “Y” to disable the BLVD function
LLVD Mode
Time,
voltage
Voltage
LLVD Volt 44.0V
BLVD Volt
40V ~ 60V
43.2V
LLVD Time 300min
BLVD Time
3 ~ 1,000
min
600min
Select “Voltage”, when the monitoring module detects that the battery
voltage is lower than the prestet “LLVD Volt”, the load will be
disconnected, and so is the battery when the battery voltage is lower
than the preset ‘BLVD Volt”.
Select “Time”, when the discharge time reaches the preset “LLVD Time”,
the monitoring module will disconnect the load; when the discharge time
reaches the preset “BLVD Time”, it will disconnect the battery
5.7.4 Charging Management Parameters
1. There are 6 related pages, as shown below:
Float: 53.5
Boost: 56.4
Limit: 0.100C10
Over: 0.300c10