Emerson 48330 Power Supply User Manual


 
58 Chapter 5 Operating SCU
ACTURA Flex 48330 Power System User Manual
Automatic Boost
Y
Cyclic Boost:
Y
To Boost
Current: 80%
Capacity: 0.06C10
Constant Boost
Current: 0.01C10
Duration: 180min
Cyclic Boost
Interval: 400h
Duration: 300min
Boost Limit
Time: 300min
Use “
” or “” to select one page or one of the parameters, and “” or “” to
select the parameter value. Press “ENT” to confirm and save.
Note
Generally you do not need to set the management value. The defaults will do.
2. The charging management parameter value description is listed below: