78 Appendix 1 System Technical Parameters
ACTURA Flex 48330 Power System User Manual
Parameter category Note
Dielectric strength
(Remove the SPD, monitoring module and rectifiers from the
system before the test.)
AC to DC circuits, AC circuit to earth: 50Hz, 3,000Vac (RMS).
DC circuit to earth: 50Hz, 1,000Vac (RMS).
Assistant circuit (not directly connected to the host circuit):
50Hz, 500Vac (RMS).
For all the three tests above, there should be no breakdown
or flashover within 1min, with leakage current not bigger than
10mA.
Others
MTBF 250,000hr
Size (mm)
600 (W)
%
600 (D)
%
2000 (H)
600 (W)
%
400
(D)
%
2000 (H)
600 (W)
%
400 (D)
%
700 (H)
Mechanica
Weight
<135kg (without
rectifiers)
<125kg (without
rectifiers)
<60kg (without
rectifiers)