Emerson 48330 Power Supply User Manual


 
44 Chapter 5 Operating SCU
ACTURA Flex 48330 Power System User Manual
Serial
No.
Alarm Description
Default
alarm level
Default
related
relay
Related parameter
configuration
14 Batt Temp Low
Battery temperature is lower than the
set value of parameter “Temp
Threshold: Low Temp”
Observation None
Low temperature alarm
point
15 Amb Temp High
Ambient temperature is higher than
the set alarm point
Observation None
16 Amb Temp Low
Ambient temperature is lower than
the alarm point
Observation None
17 No TempSensor1
Temperature sensor 1 has been set,
but no sensor is actually connected
Critical None
18 No TempSensor2
Temperature sensor 2 has been set,
but no sensor is actually connected
Critical None
19
TempSensor1
Err
Temperature sensor 1 detected
unreasonable temperature
Critical None
20 TempSensor2 Err
Temperature sensor 2 detected
unreasonable temperature
Critical None
21 LLVD
1. Load disconnection
2. Manual load disconnection
Critical 5 LLVD enabled
22 BLVD
1. When battery discharges till its
voltage is lower than the “BLVD
Volt”, or the discharge time is longer
than the “BLVD Time”, the BLVD
contactor will be open automatically
2. BLVD through manual operation
Critical 4 BLVD enabled
23 Load 1 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
24 Load 2 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
25 Load 3 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
26 Load 4 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
27 Load 5 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
28 Load 6 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
29 Load 7 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
30 Load 8 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
31 Load 9 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
32 Aux Load Fails The last route faulty Critical 6
33 Batt1 Failure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical None
34 Batt2 Failure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical None
35 Batt3 Failure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical None