Emerson M820D Power Supply User Manual


 
UM1M820BNA User Instructions
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B)
Spec No. 1M820DNA (Model M820D)
100 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Temp Comp Clamp: Enables or disables the temperature compensation voltage clamp
feature.
Temp Comp Max V: Upper voltage limit where battery temperature compensation clamps
the voltage.
Temp Comp Min V: Lower voltage limit where battery temperature compensation clamps
the voltage.
Capacity Menu
Menu Navigation: Main Menu / Settings / Battery / Capacity
Note: For WEB Interface; menu items are found under Device Information / Battery Group /
Settings Tab.
"Capacity" Parameter Settings:
Charging Eff: Value used to calculate remaining capacity of the battery.
Time 0.1C10: Discharge time with a discharge current of 0.1C10.
Time 0.2C10: Discharge time with a discharge current of 0.2C10.
Time 0.3C10: Discharge time with a discharge current of 0.3C10.
Time 0.4C10: Discharge time with a discharge current of 0.4C10.
Time 0.5C10: Discharge time with a discharge current of 0.5C10.
Time 0.6C10: Discharge time with a discharge current of 0.6C10.
Time 0.7C10: Discharge time with a discharge current of 0.7C10.
Time 0.8C10: Discharge time with a discharge current of 0.8C10.
Time 0.9C10: Discharge time with a discharge current of 0.9C10.
Time 1.0C10: Discharge time with a discharge current of 1.0C10.
Battery # Menu
Menu Navigation: Main Menu / Settings / Battery / Battery #
Note: For WEB Interface; menu items are found under Device Information / Battery Group / Battery
# / Settings Tab.
"Battery #" Parameter Settings:
Rated Capacity: Enter the battery string’s rated capacity.
Shunt Current: Enter the battery string’s shunt current rating.
Shunt Voltage: Enter the battery string’s shunt voltage rating.
BattFuseUnit
BattFuseUnit Menu
Menu Navigation: Main Menu / Settings / BattFuseUnit
Note: For WEB Interface; menu items are found under Device Information / Battery Fuse Group /
Battery Fuse Unit / Settings Tab.
"BattFuseUnit" Parameter Settings:
Num of Bat Fuse: Designates the number of battery fuses in the system.
DC
DC Menu
Menu Navigation: Main Menu / Settings / DC