Chapter 3. Local Display Menus 109
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Fan Speed Ctrl: Temporarily sets the fan speed for all converters. Setting returns to
original when Controller is returned to the Auto mode.
Confirm ID *: Confirms the position for all converters.
Clear Conv Lost*: Clears a converter lost alarm.
Clear Comm Fail*: Clears a converter communication fail alarm.
ClrAllCommFail*: Clears all converter communication fail alarms.
Conv #1 Menu
Menu Navigation: Main Menu / Manual / Converter / CONV 1
Note: For WEB Interface; menu items are found under Device Information / Converter Group /
Converter #1 / select the Control tab.
"CONV #1" Parameter Settings:
DC On/Off Ctrl: Temporarily turns the converter’s DC output on or off. Setting returns to
original when Controller is returned to the Auto mode.
Over Volt Reset: Temporarily sets the converter’s over voltage reset feature. Setting
returns to original when Controller is returned to the Auto mode.
LED Control: Temporarily sets whether or not the converter’s local power indicator blinks
when the Controller is communicating with the converter. Setting returns to original when
Controller is returned to the Auto mode.
SMTemp
SMTemp Group Menu
Menu Navigation: Main Menu / Manual / SMTemp / SMTemp Group
Note: For WEB Interface; menu items are found under Device Information / SM Temp Group /
Control Tab.
"SMTemp Group" Parameter Settings:
Clr SMTemp Lost*: Clears an SMTemp lost alarm.
SMTemp # Menu
Menu Navigation: Main Menu / Manual / SMTemp / SMTemp #
Note: For WEB Interface; menu items are found under Device Information / SM Temp Group / SM
Temp # / Control Tab.
"SMTemp #" Parameter Settings:
Clr Probe Alm*: Clears an SMTemp probe fail alarm.
3.3.4 Quick Setting Menu
Auto/Manual
Auto/Manual Menu
Menu Navigation: Main Menu / Quick Setting / "Auto/Manual"
Note: For WEB Interface; menu items are found under Quick Settings / “Auto/Manual Setting”.
"Auto/Manual" Parameter Settings:
Auto/Man State
Auto: The Controller automatically controls the power system.