Emerson M820D Power Supply User Manual


 
UM1M820BNA User Instructions
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B)
Spec No. 1M820DNA (Model M820D)
50 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Battery Alarms
(Battery)
Battery Current Limit
Exceeded
(Ov Batt Cur Lmt)
Battery current limit point is exceeded.
--
Battery Over Current
(Batt Over Curr)
Battery is in over current.
--
Low Battery Capacity
(Low Batt Cap)
Battery has low capacity.
Check the batteries.
SMDU Battery Alarms (SM-DU Module must be present in system)
(SMDU Battery)
Exceed Current Limit
(Exceed Curr Lmt)
Battery current limit point is exceeded.
--
Over Battery Current
(Over Current)
Battery is in over current.
--
Low Capacity
(Low Capacity)
Battery has low capacity.
Check the batteries.
EIB (Extended Interface Board) Battery Alarms (EIB Board must be present in system)
(EIB Battery)
Battery Current Limit
Exceeded
(Ov Bat Curr Lmt)
Battery current limit point is exceeded.
--
Battery Over Current
(Bat Over Curr)
Battery is in over current.
--
Battery Low Capacity
(Low Batt Cap)
Battery has low capacity.
Check the batteries.
SM Battery Alarms (SM-BAT Module must be present in system)
(SM Battery)
Exceed Batt Current Limit
(Over Curr Limit)
Battery is in over current.
--
Over Battery Current
(Over Batt Curr)
Battery current is high.
--
Battery Leakage
(Battery Leakage)
Battery has leakage current.
Check the batteries.
Low Acid Level
(Low Acid Level)
Battery has low acid level.