"Batt Group" Parameter Settings:
EQ/FLT Control*: Places the system in Equalize Charge or Float Charge mode.
BattTestControl*: Starts or stops a Battery Test.
Reset Batt Cap*: Resets the battery capacity calculation.
Clr Bad Bat Alm*: Clears a bad battery alarm.
Clr LiBatt Lost*: Clears a Li-Ion battery lost alarm.
ClrLiBatComFail*: Clears a Li-Ion battery communications fail alarm
Clear AbnlCur Alm*: Clears an abnormal current alarm.
Clear Cur Imb Alm*: Clears a current imbalance alarm.
ClrBatTestFail*: Clears a battery test fail alarm.
LVD
LVD Unit Menu
Menu Navigation: Main Menu / Manual / LVD / LVD Unit
Note: For WEB Interface; menu items are found under Device Information / LVD Group / LVD Unit
/ select the Control tab.
"LVD Unit" Parameter Settings:
LVD1 Control: Temporarily connects or disconnects LVD1. Setting returns to original
when Controller is returned to the Auto mode.
LVD2 Control: Temporarily connects or disconnects LVD2. Setting returns to original
when Controller is returned to the Auto mode.
EIB
EIB 1 Menu
Menu Navigation: Main Menu / Manual / EIB / EIB1
Note: For WEB Interface; menu items are found under Device Information / EIB Group / EIB 1 /
select the Control tab.
"EIB 1" Parameter Settings: (EIB1 refers to the first Extended Interface Board (EIB) in the
system.))
Relay Output 9 through 13: Temporarily sets the relay to active or not active. Setting
returns to original when Controller is returned to the Auto mode.
Converter
All Conv Ctrl Menu
Menu Navigation: Main Menu / Manual / Converter / All Conv Ctrl
Note: For WEB Interface; menu items are found under Device Information / Converter Group /
select the Control tab.
"All Conv Ctrl" Parameter Settings:
Converter Trim: Temporarily sets the output voltage for all converters. Setting reverts to
original when Controller is returned to the Auto mode.
DC On/Off Ctrl: Temporarily turns the DC output on or off for all converters. Setting returns
to original when Controller is returned to the Auto mode.
Conv LED Control: Temporarily sets whether or not a converter’s local power indicator
blinks when the Controller is communicating with the converter. Setting returns to original
when Controller is returned to the Auto mode.