Emerson M820D Power Supply User Manual


 
User Instructions UM1M820BNA
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013
Spec No. 1M820DNA (Model M820D)
Chapter 3. Local Display Menus 89
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page)
Local Menu Flow Diagrams
ESC
B5
ENT
EIB
EIB 1
Shunt 1 Current
500.0 A (50.0-50000.0)
Shunt 1 Voltage
75.0 mV (1.0-150.0)
Shunt 2 Current
500.0 A (50.0-50000.0)
Shunt 2 Voltage
75.0 mV (1.0-150.0)
Shunt 3 Current
500.0 A (50.0-50000.0)
Shunt 3 Voltage
75.0 mV (1.0-150.0)
Num Batt Shunts
0 (0-3)
Num Load Shunts
0 (0-3)
Voltage Type
48 (Block 4) (disable / 24 (block 2) /
midpoint / 48 (block 4))
Blk V Diff(12V)
1 (0- 2)
Blk V Diff(Mid)
1 (0- 2)
Block In-Use
0 (0-8)
EIB 1
ESC
B7
ENT
SMTemp
SMTemp 1
T1 Assign Equip
Ambient ( N one / Battery /Ambient)
...
T8 Assign Equip
None (None / Battery /Ambient)
SMTemp 1
ESC
B6
ENT
SMDU
SMDU 1
Shunt 1 Voltage
75 mV (25-75)
Shunt 1 Current
500 A (100-2000)
Shunt 2 Voltage
75 mV (25-75)
Shunt 2 Current
500 A (100-2000)
Shunt 3 Voltage
75 mV (25-75)
Shunt 3 Current
500 A (100-2000)
Shunt 4 Voltage
75 mV (25-75)
Shunt 4 Current
500 A (100-2000)
Shunt 5 Voltage
75 mV (25-75)
Shunt 5 Current
500 A (100-2000)
SMDU 1
ESC
B4
ENT
ENT
LVD
LVD Group
LVD Unit
SMDU 1 LVD
HTD Recon Point
38.0 deg. C (20-80)
HTD Point
40.0 deg. C (20-80)
LVD Group
ESC
LVD1
Enable (enable / disable)
LVD1 Mode
Voltage (voltage / time)
LVD1 Volt
42.0 V (40-60) (20-30)
LVD1 Recon Volt
49.0 V (40-60) (20-30)
LVD1 ReconDelay
1 min (1-30)
LVD1Time
300 min (30-1000)
LVD1 Dependency
None (none / LVD1 / LVD2)
LVD2
Enable (enable / disable)
LVD2 Mode
Voltage (voltage / time)
LVD2 Volt
42.0 V (40-60) (20-30)
LVD2 Recon Volt
49.0 V (40-60) (20-30)
LVD2 ReconDelay
1 min (1-30)
LVD2Time
600 min (30-1000)
LVD2 Dependency
None (none / LVD1 / LVD2)
HTD1
Disable (enable / disable)
HTD2
Disable (enabled / disable)
LVD Type
Bistable (bistable / mono-stable / mono w/sample)
LVD Unit
LVD 1
Enable (enable / disable)
LVD 1Mode
Voltage (voltage / time)
LVD 1Voltage
42.0 V (40-60) (20-30)
LVD1 Recon Volt
49.0 V (40-60) (20-30)
LVD1 ReconDelay
1 min (1-30)
LVD 1Time
300 min (30-1000)
LVD1 Dependency
None (none / LVD1 / LVD2)
LVD 2
Enable (enable / disable)
LVD 2Mode
Voltage (voltage / time)
LVD 2Voltage
42.0 V (40-60) (20-30)
LVD2 Recon Volt
49.0 V (40-60) (20-30)
LVD2 ReconDelay
1 min (1-30)
LVD 2Time
600 min (30-1000)
LVD2 Dependency
None (none / LVD1 / LVD2)
HTD 1
Disable (enable / disable)
HTD 2
Disable (enabled / disable)
SMDU 1 LVD
ENT
ESC
ENT
ESC
Displayed when Voltage Type
set for other then disable and
Block In-Use set for other then 0.