Hitachi SJ100 Power Supply User Manual


 
“C” Group: Intelligent Terminal Functions
Configuring
Drive Parameters
3–38
Output Terminal Configuration
The inverter provides configuration for logic (discrete) and analog outputs, shown in the
table below.
The output logic convention is programmable for terminals [11], [12], and the alarm
relay terminals. The open-collector output terminals [11] and [12] default to normally
open (active low), but you can select normally closed (active high) for these terminals in
order to invert the sense of the logic. You can invert the logical sense of the alarm relay
output as well.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
Units
C_21 Terminal [11] function Select terminal [11] function,
6 options (see next section)
01
[FA1]
01
[FA1]
01
[FA1]
OUT-TM 1 FA1
C_22 Terminal [12] function Select terminal [12] function,
6 options (see next section)
00
[RUN
]
00
[RUN
]
00
[RUN
]
OUT-TM 2 RUN
C_23 [FM] signal selection Select terminal [FM] function,
3 options (see next section)
00
[A–F]
00
[A–F]
00
[A–F]
MONITOR A-F
C_24 Alarm relay terminal
function
Select alarm terminal function,
6 options (see next section)
05
[AL]
05
[AL]
05
[AL]
OUT-TM RY AL
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
Units
C_31 Terminal [11] active
state (–FU)
Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
—00——
OUT-TM O/C-1 NO
Reserved (–FE / –FR) (reserved) DO NOT EDIT 00—00—
(not displayed)
C_32 Terminal [12] active
state (–FU)
Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
—00——
OUT-TM O/C-2 NO
Terminal [11] active
state (–FE / –FR)
(reserved) DO NOT EDIT 00—00—
OUT-TM O/C-1 NO
C_33 Alarm relay active state Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
01 01 01
OUT-TM O/C-RY NO