Using the Front Panel Keypad
Inverter Mounting
and Installation
2–26
Configure the Inverter for the Number of Motor Poles- The number of magnetic
poles of a motor is determined by the motor’s internal winding arrangement. The specifi-
cations label on the motor usually indicates its number of poles. For proper operation,
verify the parameter setting matches the motor poles. Many industrial motors have four
poles, corresponding to the default setting in the inverter.
Follow the steps in the table below to verify the motor poles setting and change it if
necessary (the table resumes action from the end of the previous table.)
This step concludes the parameter setups for the inverter. You are almost ready to run the
motor for the first time!
TIP: If you became lost during any of these steps, first observe the state of the PRG
LED. Then study the
Keypad Navigational Map” on page 2–23 to determine the current
state of the keypad controls and display. As long as you do not press the STR key, no
parameters will be changed by keypad entry errors. Note that power cycling the inverter
will not cause it to reset to a particular programming state.
The next section will show you how to monitor a particular parameter from the display.
Then you will be ready to run the motor.
Action Display Func./Parameter
Press the
key.
“A” Group selected
Press the
key three times.
“H” Group selected
Press the
key.
First “H” parameter
Press the
key three times.
Motor poles parameter
Press the
key.
2 = 2 poles
4 = 4 poles (default)
6 = 6 poles
8 = 8 poles
Press the
or key as needed.
Set to match your motor (your
display may be different)
Press the
key.
Stores parameter, returns to “H”
Group list
FUNC.
A--
1
H--
FUNC.
H01
1
H04
FUNC.
4
1
2
4
STR