A_72 PID proportional gain 1.0 1.0 1.0
A_73 PID integral time constant 1.0 1.0 1.0
A_74 PID derivative gain 0.0 0.0 0.0
A_75 PV scale conversion 1.00 1.00 1.00
A_76 PV source setting 00 00 00
A_81 AVR function select 02 00 02
A_82 AVR voltage select 230/400 230/460 200/400
A_92 Acceleration (2) time setting 15.0 15.0 15.0
A292 Acceleration (2) time setting,
(2nd motor)
15.0 15.0 15.0
A_93 Deceleration (2) time setting 15.0 15.0 15.0
A293 Deceleration (2) time setting,
(2nd motor)
15.0 15.0 15.0
A_94 Select method to switch to Acc2/
Dec2 profile
00 00 00
A294 Select method to switch to Acc2/
Dec2 profile, 2nd motor
00 00 00
A_95 Acc1 to Acc2 frequency transi-
tion point
0.0 0.0 0.0
A295 Acc1 to Acc2 frequency transi-
tion point, 2nd motor
0.0 0.0 0.0
A_96 Dec1 to Dec2 frequency transi-
tion point
0.0 0.0 0.0
A296 Dec1 to Dec2 frequency transi-
tion point, 2nd motor
0.0 0.0 0.0
A_97 Acceleration curve selection 00 00 00
A_98 Deceleration curve selection 00 00 00
“A” Group Parameters Default Setting
User
Setting
Func.
Code
Name
-FE
(Europe)
-FU
(USA)