Hitachi SJ100 Power Supply User Manual


 
“H” Group: Motor Constants Functions
Configuring
Drive Parameters
3–44
H204 Motor poles setting, 2nd
motor
Four selections:
2 / 4 / 6 / 8
4 4 4 poles
2AUXP 4p
H_05 Motor speed constant Motor proportional gain
constant (factory set),
range is 0 to 99
20 20 20
AUX KP 20
H205 Motor speed constant,
2nd motor
Motor proportional gain
constant (factory set)
range is 0 to 99
20 20 20
2AUXKP 20
H_06 Motor stabilization
constant
Motor constant (factory set),
range is 0 to 255
100 100 100
AUX KCD 100
H206 Motor stabilization
constant, 2nd motor
Motor constant (factory set),
range is 0 to 255
100 100 100
2AUXKCD 100
H_20 Motor constant R1 Range is 0.000 to 65.53,
0.000 to 9.999
10.00 to 65.53
Factory set according
to inverter model
Ohms
AUX R1 05.700*
H220 Motor constant R1, 2nd
motor
Range is 0.000 to 65.53,
0.000 to 9.999
10.00 to 65.53
Factory set according
to inverter model
Ohms
2AUXR1 05.700*
H_21 Motor constant R2 Range is 0.000 to 65.53,
0.000 to 9.999
10.00 to 65.53
Factory set according
to inverter model
Ohms
AUX R2 02.773
H221 Motor constant R2, 2nd
motor
Range is 0.000 to 65.53,
0.000 to 9.999
10.00 to 65.53
Factory set according
to inverter model
Ohms
2AUXR2 02.773
H_22 Motor constant L Range is 0.00 - 655.3 mH,
0.00 to 99.99
100.0 - 655.3
Factory set according
to inverter model
mH
AUX L 045.70mH
H222 Motor constant L,
2nd motor
Range is 0.00 - 655.3 mH,
0.00 to 99.99
100.0 - 655.3
Factory set according
to inverter model
mH
2AUXL 045.70mH
H_23 Motor constant I
o
Range is 0.00 to 655.3 Amps,
0.00 to 99.99
100.0 - 655.3
Factory set according
to inverter model
Arms
AUX I0 001.50A
H223 Motor constant I
o
, 2nd
motor
Range is 0.00 to 655.3 Amps,
0.00 to 99.99
100.0 - 655.3
Factory set according
to inverter model
Arms
2AUXI0 001.50A
“H” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
Units