Analog Input Calculate Function – The inverter can mathematically combine two
input sources into one value. The Calculate function can either add, subtract, or multiply
the two selected sources. This provides the flexibility needed by various applica-
tions.You can use the result for the output frequency setting (use A001=10) or for the
PID Process Variable (PV) input (use A075=03).
A141
[O] input
Potentiometer
[OI] input
Network variable
Digital operator
[O] input
Potentiometer
[OI] input
Network variable
Digital operator
A142
A input select
A143
• 00 A + B
• 01 A – B
• 02 A x B
A
B
“CAL”
(result)
B input select
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF
(EU)
–FU
(USA)
Units
A141 A input select for
calculate function
Five options:
00...Digital operator
01...Keypad potentiometer
02...[O] input
03...[OI] input
04...Network variable
✘ 02 02 —
CALC Slct1 O
A142 B input select for
calculate function
Five options:
00...Digital operator
01...Keypad potentiometer
02...[O] input
03...[OI] input
04...Network variable
✘ 03 03 —
CALC Slct2 OI
A143 Calculation symbol Calculates a value based on the
A input source (A141 selects)
and the B input source (A142
selects). Three options:
00...ADD (A input + B input)
01...SUB (A input – B input)
02...MUL (A input x B input)
✘ 00 00 —
CALC SMBL ADD