SJ200 Inverter
Appendix B
B–5
6. Inverter Parameter Setup - The inverter has several settings related to ModBus
communications. The table below lists them together. The Required column indicates
which parameters must be set properly to allow communications. You may need to
refer to the host computer documentation in order to match some of its settings.
NOTE: When you edit and store any of the parameters above, the inverter causes it to
take effect immediately. ModBus transmission occurs only after you set the OPE/485
DIP switch to the “485” position and turn on the inverter. Note that parameters C071 to
C078 cannot be changed via the network. To edit them, reconnect the inverter keypad (or
other digital operator) and edit the parameters.
Func.
Code
Name Required Settings
A001 Frequency source setting ✔ 00 .. Keypad potentiometer
01 .. Control terminal
02 .. Function F001 setting
03 .. ModBus network input
10 .. Calculate function output
A002 Run command source setting ✔ 01 .. Control terminal
02 .. Run key on keypad, or
digital operator
03 .. ModBus network input
C071 Communication speed selection ✔ 04 .. 4800 bps
05 .. 9600 bps
06 .. 19200 bps
C072 Node allocation ✔ Network address, range is 1 to 32
C074 Communication parity selection ✔ 00 .. No parity
01 .. Even parity
02 .. Odd parity
C075 Communication stop bit selection ✔ Range is 1 to 2
C076 Communication error select — 00 .. Trip (error code E60)
01 .. Decelerate to a stop and trip
(error code E60)
02 .. Disable
03 .. Free run stop (coasting)
04 .. Decelerate to a stop
C077 Communication error time-out — Comm. watchdog timer period,
range is 0.00 to 99.99 sec.
C078 Communication wait time ✔ Time the inverter waits after receiv-
ing a message before it transmits.
Range is 0. to 1000. ms