Hitachi SJ200 Series Power Supply User Manual


 
SJ200 Inverter
Appendix B
B–35
Note 1: Assume that the inverter current rating is 10000 (for B013/B213).
B130 Over-voltage
LADSTOP enable
R/W Pauses deceleration ramp when
DC bus voltage rises above
threshold level, in order to
avoid over-voltage trip.
Two option codes:
00...Disable
01...Enable
00A4h 0, 1
B140 Over-current trip
suppression
R/W Two option codes:
00...Disable
01...Enable
00A5h 0, 1
B150 Carrier mode (not
accessible to ModBus)
Automatically reduces the
carrier frequency as the
ambient temperature increases.
Two option codes:
00...Disable
01...Enable
00A6h 0, 1
“B” Group Fine Tuning Functions
Func.
Code
Name R/W Description
Network Data