Hitachi SJ200 Series Power Supply User Manual


 
SJ200 Inverter
Operations
and Monitoring
4–47
Option
Code
Terminal
Symbol
Function Name
Output
State
Description
07 FBV Feedback Value
Check
ON
Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is
less than the Feedback Low Limit (C053)
OFF
Transitions to OFF when the PID Feedback
Value (PV) exceeds the PID High Limit
(C052)
Transitions to OFF when the inverter goes
from Run Mode to Stop Mode
Valid for outputs:
11, 12, AL0 – AL2
Required settings:
A076, C052, C053
Notes:
The [FBV] is designed for implementing two-stage
control. The PV high limit and PV low limit param-
eters, C052 and C053, do not function as process
alarm thresholds. Terminal [FBV] does not provide
a PID alarm function.
The example circuit for terminal [12] drives a relay
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from
damaging the inverter’s output transistor.
RY
+
12 11LH O
OI FM
CM2
Example (requires output configuration—
see page 3–46
):
Inverter output
terminal circuit
FBV
Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
see pages
4–35 and 3–46):
AL0
AL2AL1
Inverter logic
circuit board
See I/O specs
on page 4–6
.
FBV
Load
Power
supply