Hitachi SJ200 Series Power Supply User Manual


 
ModBus Data Listing
Appendix B
B–34
B085 Country code for initial-
ization (not accessible
to ModBus)
Select default parameter values
for country on initialization.
Note: Write not allowed from
network.
009Bh
B086 Frequency scaling
conversion factor
R/W Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9
009Ch 1 to 999 0.1
B087 STOP key enable R/W Select whether the STOP key
on the keypad is enabled, two
option codes:
00...enabled
01...disabled
009Dh 0, 1
B088 Restart mode after FRS R/W Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00...Restart from 0Hz
01...Restart from frequency
detected from real speed of
motor (frequency matching)
009Eh 0, 1
B090 Dynamic braking usage
ratio
R/W Selects the rate of use (in %) of
the regenerative braking
resistor per 100 sec. intervals,
range is 0.0 to 100.0%
0% .Dynamic braking disabled
>0% Enabled, per value
009Fh 0 =
disabled
, 1 to
1000
enabled
0.1 %
B091 Stop mode selection R/W Selects how the inverter stops
the motor, two option codes:
00...DEC (decelerate and stop)
01...FRS (free run to stop)
00A0h 0, 1
B092 Cooling fan control R/W Selects when the fan is ON per
inverter operation, two options:
00...Fan is always ON
01...Fan is ON during run,
OFF during stop (5 min.
delay from ON to OFF)
02...Fan is temperature
controlled
00A1h 0, 1, 2
B095 Dynamic braking
control
R/W Three option codes:
00...Disable
01...Enable during RUN only
02...Enable always
00A2h 0, 1, 2
B096 Dynamic braking
activation level
R/W Range is:
330 to 380V (200V class),
660 to 760V (400V class)
00A3h 330 to
380, 660
to 760
1 V
“B” Group Fine Tuning Functions
Func.
Code
Name R/W Description
Network Data
Reg. Range Res.