Note 1: When the value is 10000 (100.0 seconds), a value in the second decimal place
is ignored (for A092/A292 and A093/A293).
A141 A input select for calcu-
late function
R/W Five options:
00...Digital operator
01...Keypad potentiometer
02...[O] input
03...[OI] input
04...Network variable
00E3h 0 to 4
A142 B input select for calcu-
late function
R/W Five options:
00...Digital operator
01...Keypad potentiometer
02...[O] input
03...[OI] input
04...Network variable
00E4h 0 to 4
A143 Calculation symbol R/W Calculates a value based on the
A input source (A141 selects)
and the B input source (A142
selects). Three options:
00... ADD (A input + B input)
01...SUB (A input – B input)
02...MUL (A input x B input)
00E5h 0 1, 2
A145 ADD frequency R/W An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
00E6h 0 to 4000 0.1 Hz
A146 ADD direction select R/W Two options:
00...Plus (adds A145 value to
the output frequency setting)
01...Minus (subtracts A145
value from the output
frequency setting)
00E7h 0, 1
Holding Registers for “A” Group Standard Functions
Func.
Code
Name R/W Description
Network Data