SJ200 Inverter
Appendix B
B–29
A077 Reverse PID action R/W Two option codes:
00...PID input = SP – PV
01...PID input = –(SP – PV)
00E1h 0, 1 —
A078 PID output limit R/W Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0%
00E2h 0 to 1000 0.1 %
A081 AVR function select R/W Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
00...AVR enabled
01...AVR disabled
02...AVR enabled except
during deceleration
0072h 0, 1, 2 —
A082 AVR voltage select R/W 200V class inverter settings:
00...200
01...215
02...220
03...230
04...240
400V class inverter settings:
00...380
01...400
02...415
03...440
04...460
05...480
0073h 0 to 5 —
A092
(high)
Acceleration (2) time
setting
R/W Duration of 2nd segment of
acceleration, range is:
0.01 to 3000 sec.
0074h 1 to
300000
*1
0.1 sec
A092
(low)
R/W 0075h
A292
(high)
Acceleration (2) time
setting, (2nd motor)
R/W Duration of 2nd segment of
acceleration, 2nd motor,
range is: 0.01 to 3000 sec
0076h 1 to
300000
*1
0.1 sec
A292
(low)
R/W 0077h
A093
(high)
Deceleration (2) time
setting
R/W Duration of 2nd segment of
deceleration, range is:
0.01 to 3000 sec.
0078h 1 to
300000
*1
0.1 sec
A093
(low)
R/W 0079h
A293
(high)
Deceleration (2) time
setting, (2nd motor)
R/W Duration of 2nd segment of
deceleration, range is:
0.01 to 3000 sec.
007Ah 1 to
300000
*1
0.1 sec
A293
(low)
R/W 007Bh
Holding Registers for “A” Group Standard Functions
Func.
Code
Name R/W Description
Network Data
Reg. Range Res.