Hitachi SJ200 Series Power Supply User Manual


 
SJ200 Inverter
Configuring
Drive Parameters
3–7
Trip Event and History Monitoring
The trip event and history monitoring feature lets you cycle through related information
using the keypad. See
Monitoring Trip Events, History, & Conditions” on page 6–5 for
more details.
D007 Scaled output frequency
monitor
Displays the output frequency
scaled by the constant in B086.
Decimal point indicates range:
XX.XX 0.00 to 99.99
XXX.X 100.0 to 999.9
XXXX. 1000. to 9999.
XXXX 1000 to 9999 (x10=
10000 to 99999)
Hz times
constant
F-Cnv 00000.00
D013 Output voltage monitor Voltage of output to motor,
range is 0.0 to 600.0V
—V
Vout 00000V
D016 Cumulative operation
RUN time monitor
Displays total time the inverter has
been in RUN mode in hours.
Range is 0 to 9999 /
1000 to 9999 /
Γ100 to Γ999 (10,000 to 99,900)
hours
RUN 0000000hr
D017 Cumulative power-on
time monitor
Displays total time the inverter has
been in RUN mode in hours.
Range is 0 to 9999 /
1000 to 9999 /
Γ100 to Γ999 (10,000 to 99,900)
hours
ON 0000000hr
“D” Function
Run
Mode
Edit
Units
Func.
Code
Name /
SRW Display
Description
“D” Function
Run
Mode
Edit
Units
Func.
Code
Name /
SRW Display
Description
D080 Trip counter Number of trip events,
range is 0. to 9999
events
ERR CNT 00000
D081 Trip monitor 1 Displays trip event informa-
tion:
Error code
Output freq. at trip point
Motor current at trip point
DC bus voltage at trip point
Cumulative inverter opera-
tion time at trip point
Cumulative power-ON time
at trip point
——
ERR 1 ########
D082 Trip monitor 2
ERR 2 ########
D083 Trip monitor 3
ERR 3 ########