Using Intelligent Input Terminals
Operations
and Monitoring
4–32
ADD Frequency Enable
The inverter can add or subtract an offset value to the output frequency setting which is
specified by A001 (will work with any of the five possible sources). The ADD
Frequency is a value you can store in parameter A145. The ADD Frequency is summed
with or subtracted from the output frequency setting only when the [ADD] terminal is
ON. Function A146 selects whether to add or subtract. By configuring an intelligent
input as the [ADD] terminal, your application can selectively apply the fixed value in
A145 to offset (positively or negatively) the inverter output frequency in real time.
A001
Function F001 setting
Control terminal
ModBus network input
Calculate function output
Keypad potentiometer
A145
+
∑
+/–
ADD frequency
Frequency source setting
Output frequency setting
[ADD]Intelligent input
A146
ADD direction select
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
50 ADD ADD Frequency
Enable
ON Applies the A145 Add Frequency value to the
output frequency.
OFF Does not apply the Add Frequency. The output
frequency retains its normal value.
Valid for inputs:
C001, C002, C003, C004,
C005, C006
Required settings:
A001, A145, A146
Notes:
•
A001 may specify any source; the Add Frequency
will be added to or subtracted from that value to
yield the output frequency value.
123456L
PCS
Example (requires input configuration—see
page 3–41
):
See I/O specs on page 4–6
.
ADD