Hitachi SJ200 Series Power Supply User Manual


 
“A” Group: Standard Functions
Configuring
Drive Parameters
3–24
Second Acceleration and Deceleration Functions
The SJ200 inverter features two-stage acceleration and deceleration ramps. This gives
flexibility in the profile shape. You can specify the frequency transition point, the point
at which the standard acceleration (F002) or deceleration (F003) changes to the second
acceleration (A092) or deceleration (A093). Or, you can use intelligent input [2CH] to
trigger this transition. These profile options are also available for the second motor
settings. Select a transition method via A094 as depicted below. Be careful not to
confuse the second acceleration/deceleration settings with settings for the second
motor!
Accel 1
Accel 2
2CH
input
Frequency
transition point
A95
A094
=
00 A094
=
01
Output
frequency
Output
frequency
t
t
Accel 1
Accel 2
t
Transition via 2CH input Transition via freq. level
00
1
0
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF
(EU)
–FU
(USA)
Units
A092 Acceleration (2) time
setting
Duration of 2nd segment of
acceleration, range is:
0.01 to 3000 sec.
15.00 15.00 sec.
ACC 2 0015.00s
A292 Acceleration (2) time
setting, (2nd motor)
Duration of 2nd segment of
acceleration, 2nd motor,
range is: 0.01 to 3000 sec.
15.00 15.00 sec.
2ACC2 015.00s
A093 Deceleration (2) time
setting
Duration of 2nd segment of
deceleration, range is:
0.01 to 3000 sec.
15.00 15.00 sec.
DEC 2 015.00s
A293 Deceleration (2) time
setting, (2nd motor)
Duration of 2nd segment of
deceleration, 2nd motor,
range is: 0.01 to 3000 sec.
15.00 15.00 sec.
2DEC2 015.00s
A094 Select method to switch
to Acc2/Dec2 profile
Two options for switching
from 1st to 2nd accel/decel:
00...2CH input from terminal
01...transition frequency
00 00
ACC CHG TM
A294 Select method to switch
to Acc2/Dec2 profile,
2nd motor
Two options for switching
from 1st to 2nd accel/decel:
00...2CH input from terminal
01...transition frequency
(2nd motor)
00 00
2ACCCHG TM