ModBus Data Listing
Appendix B
B–38
C082 OI input span calibra-
tion
R/W Scale factor between the
external frequency command
on terminals L – OI (current
input) and the frequency
output, range is 0.0 to 200.0%
00C8h 0 to 2000 0.1 %
C085 Thermistor input tuning R/W Range is 0.0 to 200.0% 00EEh 0 to 2000 0.1 %
C086 [AM] terminal offset
tuning
R/W Range is 0.0 to 10.0V 00C9h 0 to 100 0.1 V
C091 Debug mode enable — Displays debug parameters.
Two option codes:
00...Disable
01...Enable
———
C101 Up/Down memory
mode
selection
R/W Controls speed setpoint for the
inverter after power cycle. Two
option codes:
00...Clear last frequency
(return to default frequency
F001)
01...Keep last frequency
adjusted by UP/DWN
00CFh 0, 1 —
C102 Reset selection R/W Determines response to Reset
input [RST].
Three option codes:
00...Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01...Cancel trip state at signal
OFF transition, stops inverter if
in Run Mode
02...Cancel trip state at input
signal ON transition, no effect
if in Run Mode
00D0h 0, 1, 2 —
C141 Input A select for logic
output
R/W
See
“Output Logic and
Timing” on page 3–53
00EFh 0, 1, 2, 3,
4, 5, 6, 7,
8, 9
—
C142 Input B select for logic
output
R/W 00F0h
C143 Logic function select R/W Applies a logic function to
calculate [LOG] output state,
three options:
00... [LOG] = A AND B
01...[LOG] = A OR B
02...[LOG] = A XOR B
00F1h 0, 1, 2 —
C144 Terminal [11] ON delay R/W Range is 0.0 to 100.0 sec. 00F2h 0 to 1000 0.1 sec
C145 Terminal [11] OFF
delay
R/W Range is 0.0 to 100.0 sec. 00F3h 0 to 1000 0.1 sec
“C” Group Intelligent Terminal Functions
Func.
Code
Name R/W Description
Network Data
Reg. Range Res.