SJ200 Inverter
Inverter Mounting
and Installation
2–29
If the Potentiometer Enable LED is OFF, follow the steps below.
Select the Keypad for the RUN Command - The RUN
command causes the inverter to accelerate the motor to
the selected speed. The Run command can arrive from
various sources, including the control terminals, the Run
key on the keypad, or the network. In the figure to the
right, notice the Run Key Enable LED, just above the
Run key. If the LED is ON, the Run key is already
selected as the source, and you may skip this step. Note
that the default setting depends on the country.
If the Potentiometer Enable LED is OFF, follow the steps below (the table resumes
action from the end of the previous table).
NOTE: After completing the steps above, the Run Key Enable LED will be ON. This
does not mean the motor is trying to run; it means that the RUN key is now enabled.
DO NOT press the RUN key at this time—complete the parameter setup first.
Action Display Func./Parameter
(Starting point) “A” Group selected
Press the
key.
Speed command source setting
Press the
key again.
00 = Keypad potentiometer
01 = Control terminals
02 = Function F001 setting
03 = ModBus network
10 = Calculate function output
Press the
key.
00 = potentiometer (selected)
Press the
key.
Stores parameter, returns to “A”
Group list
Action Display Func./Parameter
(Starting point) Speed command source setting
Press the
key once.
Run command source setting
Press the
key.
01 = control terminals
02 = Run key on keypad
03 = ModBus network input
Press the
key.
02 = keypad (selected)
Press the
key.
Stores parameter, returns to “A”
Group list
A–––
FUNC.
A001
FUNC.
01
2
00
STR
A001
POWER
RUN
PRG
RUN
STOP
RESET
HITACHI
FUNC
STR
1
2
50.0
Hz
A
HITACHI
ALARM
Run Key Enable LED
A001
1
A002
FUNC.
01
1
02
STR
A002