Temperature checkout
Proper cooling of the system is important for proper operation and system reliability.
For a typical Netfinity server, you should make sure:
Each of the drive bays has either a drive or a filler panel installed
The top cover is in place during normal operation
There is at least 50 mm (2 inches) of ventilated space at the sides of the server and
100 mm (4 inches) at the rear of the server
The top cover is removed for no longer than 30 minutes while the server is
operating
A removed hot-swap drive is replaced within two minutes of removal
Cables for optional adapters are routed according to the instructions provided
with the adapters (ensure that cables are not restricting air flow)
The fans are operating correctly and the air flow is good
A failed fan is replaced within 48 hours
In addition, ensure that the environmental specifications for the system are met. See
Features and specifications on page 4.