126
(35)CH Unused channel setting (Un\G61, Un\G93, Un\G125, Un\G157)
Set this buffer memory area when treating channels that do not control temperature or are not connected with
temperature sensors as "Unused". Setting them as unused channels stops detection of an alert.
For details on the unused channel setting, refer to the following.
Page 297, Section 5.5
(a) Setting range
• 0: Use
• 1: Unused
(b) Default value
The default values are set to Use (0) in all channels.
(c) ON of Default setting registration instruction (Yn9) ( Page 58, Section 3.3.3 (5))
When Default setting registration instruction (Yn9) is turned on from off, CH Unused channel setting
(Un\G61, Un\G93, Un\G125, Un\G157) is reset to Use (0).
Channels that do not control temperature or are not connected to temperature sensors needs to be set as
unused channels again after settings of other buffer memory areas and non-volatile memories return to the
default values. Set CH Unused channel setting (Un\G61, Un\G93, Un\G125, Un\G157) to Unused (1) again.
Common