Mitsubishi Electronics Q64TCTTN Network Card User Manual


 
324
(b) Parameter setting
Set the contents of initial settings in the parameter.
1. Open the "Parameter" window.
Project window [Intelligent Function Module] [Q64TCTTN] [Parameter]
2. Click to set items unnecessary for the mode set on Switch Setting to 0.
3. Set the parameter.
Item Description
Set value
CH1 CH2 CH3 CH4
Input range
Set the temperature sensor
used for the Q64TCN and the
measurement range.
2: Thermocouple
K Measured
Temperature
Range (0 to
1300°C)
2: Thermocouple
K Measured
Temperature
Range (0 to
1300°C)
2: Thermocouple
K Measured
Temperature
Range (0 to
1300°C)
2: Thermocouple
K Measured
Temperature
Range (0 to
1300°C)
Set value (SV)
setting
Set the target temperature
value of PID control.
200°C 250°C 300°C 350°C
Unused channel
setting
Configure this setting when the
channels where the
temperature control is not
performed and the temperature
sensor is not connected are set
to be unused.
0: Used 0: Used 0: Used 0: Used
Control output cycle
setting/Heating
control output cycle
setting
Set the pulse cycle (ON/OFF
cycle) of the transistor output.
20s 20s 20s 20s