Mitsubishi Electronics Q64TCTTN Network Card User Manual


 
323
CHAPTER 7 PROGRAMMING
7
7.2 When Using the Module in a Standard System Configuration
7.2.2 Standard control (peak current suppression function, simultaneous temperature rise function)
(5) Contents of the initial setting
*1 Configure this setting only when the simultaneous temperature rise function is used.
*2 Configure this setting only when the peak current suppression function is used.
(6) When using the parameter of an intelligent function module
(a) Devices used by a user
Item
Description
CH1 CH2 CH3 CH4
Input range
2: Thermocouple K
Measured
Temperature Range
(0 to 1300°C)
2: Thermocouple K
Measured
Temperature Range
(0 to 1300°C)
2: Thermocouple K
Measured
Temperature Range
(0 to 1300°C)
2: Thermocouple K
Measured
Temperature Range
(0 to 1300°C)
Set value (SV) setting 200°C 250°C 300°C 350°C
Unused channel setting 0: Used 0: Used 0: Used 0: Used
Control output cycle setting 20s 20s 20s 20s
Simultaneous temperature
rise group setting*1
1: Group 1 1: Group 1 2: Group 2 2: Group 2
Peak current suppression
control group setting*2
1: Group 1 2: Group 2 3: Group 3 4: Group 4
Simultaneous temperature
rise AT mode selection*1
1: AT for
Simultaneous
Temperature Rise
1: AT for
Simultaneous
Temperature Rise
1: AT for
Simultaneous
Temperature Rise
1: AT for
Simultaneous
Temperature Rise
Alert 1 mode setting
1: Upper Limit Input
Alert
1: Upper Limit Input
Alert
1: Upper Limit Input
Alert
1: Upper Limit Input
Alert
Alert set value 1 250°C 300°C 350°C 400°C
Device Description
X10 Module READY flag
Q64TCTTN (X10 to X1F)
X12 Write error flag
X22 Error code reset instruction
QX42 (X20 to X5F)
X23 Operation mode setting instruction
X24
E
2
PROM's PID constants read instruction
Y11 Setting/operation mode instruction
Q64TCTTN (Y10 to Y1F)
Y12 Error reset instruction
Y18
E
2
PROM backup instruction
Y1B Setting change instruction
Y60 to Y6F Error code output QY42P (Y60 to Y9F)
D50 Error code
Devices where data is written
by auto refresh
D51 to D54 CH Temperature process value (PV)
D55 to D58 CH Alert definition
M20 to M23 CH Read completion flag
M24 to M27 CH Write completion flag